LT160-N-120VAC
Interface Card
for the Allen-Bradley Bulletin 160 Adjustable
Frequency Drive
Description
The 120 VAC interface module mounts on standard din
rail 4 inches in front of the drive or it can be
mounted on either side of the drive with 1 inch
clearance. It is suitable for all 460 Volt and 230 Volt
drives. It allows the use of 120 VAC for all control
logic inputs for the SF1 model and adds SW1, SW2, and
SW3 for the PS1 model.
Installation
1. Remove all power from the drive at L1, L2, L3
terminals.
2. Verify that the power is off, before proceeding.
3. Connect power, ground and motor wires to the Power
Terminal Block.
4. Loosen the screws on the Control Terminal Block to
allow the 8 conductor ribbon cable to slide into
terminal blocks, 1 through 8 tighten accordingly. (For
SF1 models, connect only 4 conductors of the ribbon
cable to terminals 5 through 8 , cut or fold back
conductors 1 through 4.)
5. Terminate the control logic signals to the terminal
block TB1 on the interface module. See Leaf Technology
Drawing LT160-N-120VAC for wire placement.
Note: If the control logic signals
originate from a triac or noise suppressed source, any
off state leakage current must be reduced to below
3ma.. A 4.7K ohm, 10 Watt resistor installed between
the input signal and L2 will usually reduce the leakage
current to the appropriate level. This resistor must be
mounted external the drive.
6. Make sure that no control logic voltage is present
and apply power to the terminals L1, L2 and L3.
7. Program drive per instructions in the 160 SSC user
manual (Publication 160-5.0).
8. Apply power to TB1 control circuits.
Specifications
Input Voltage(120 VAC) Input Loading(3ma.) Turn On/Off
(70VAC +/- 15%)
Bd. Spec. FL-GFN-062-C-2/2-A3A Mat. NEMA FR-4
per UL94
Caution:This card contains electrostatic sensitive
devices. The installer should be grounded before
handling the card.
®
2011 Leaf Technology, Inc., All Rights
Reserved
Phone: 262.369.2260
E-mail: leaftech@leaftech.com
|